Cable design
Conductor: fine wire strands of tinned copper wires,according IEC 60228,Class 5
Insulation: irradiation cross-linkable LSZH flame retardant polyolefin compound
Outer jacket: irradiation cross-linkable LSZH flame retardant polyolefin compound resistance against water , UV resistant
Temperature range
Max,temperature at conductor -40°C up to +120°C
Temperature range -40°C up to +90°C
Electrical characteristics
Nominal voltage: AC 600/1000V,DC 900/1800V
AC-test-voltage: 6.5KV
Application
SOLAR CABLE used for interconnection wiring of grounded and ungrounded photovoltaic power systems
Single-Core Solar Cable | |||||
Cable Size (mm2) | Conductor Strand (mm) | Nominal insulation thickness (mm) | Nominal sheath thickness (mm) | Overall Dia (mm) | Max. Conductor Resis(20ºC) (Ω/Km) |
1×2.5 | 49/0.25 | 0.8 | 0.8 | 5.4±0.3 | 8.21 |
1×4 | 56/0.30 | 0.8 | 0.9 | 6.2±0.3 | 5.09 |
1×6 | 84/0.30 | 0.8 | 0.9 | 6.8±0.3 | 3.39 |
1×10 | 84/0.40 | 1.0 | 1.0 | 9.0±0.3 | 1.95 |
1×16 | 126/0.40 | 1.0 | 1.0 | 10.0±0.3 | 1.24 |
1×25 | 196/0.40 | 1.2 | 1.2 | 12.2±0.5 | 0.795 |
1×35 | 276/0.40 | 1.2 | 1.2 | 13.6±0.5 | 0.565 |